MYREAL Anti-Condensation Rubber Insulation Pipe for Energy Saving Chilled Lines
Basic Properties
Trading Properties
| Product Name: | High Vapour Resistance Anti-Condensation Insulation Pipe | Application: | Energy Saving Chilled Water Lines |
|---|---|---|---|
| Inner Diameter: | 13-89 Mm | Wall Thickness: | 20-35 Mm |
| Nominal Density: | 72 Kg/m3 | Thermal Conductivity: | <=0.034 W/(m.K) At 0 C |
| Water Vapour Diffusion Resistance: | >=10,000 | Water Absorption: | <=10 % By Volume |
| Fire Rating: | B1 / Class 0 | Length Per Piece: | 2 M |
Dripping chilled water lines are usually blamed on the insulation being too thin, but the real cause is often a vapour barrier that was never continuous. This anti-condensation rubber insulation pipe addresses both: a closed cell wall that blocks vapour, and a wall thickness range up to 32 mm that keeps the outer surface above dew point in humid plant rooms.
Anti-condensation performance is a system property, so the tube is supplied with matching adhesive and self-adhesive lap tape. Every joint, termination and fitting is closed with the same material, giving a continuous vapour barrier from the plant room to the last fan coil.
High water vapour resistance above 10,000 and water absorption below 10 % by volume mean the insulation still works after years of cycling between cold operation and shutdown. That is where open cell materials fail: they absorb moisture during shutdown, and the thermal conductivity rises permanently.
Low thermal conductivity of 0.034 W/(m.K) also delivers measurable energy saving on chilled lines, because a lower temperature rise between the chiller and the terminal means less pumping and less compressor work. Tubes run from 12 mm to 114 mm inner diameter in 2 m pieces with 20 mm to 35 mm wall.
| Parameter | Specification |
|---|---|
| Product | MYREAL Anti-Condensation Rubber Insulation Pipe for Energy Saving Chilled Lines |
| Model | FR-30X57 |
| Material | NBR/PVC elastomeric rubber foam, closed cell |
| Colour | Black |
| Nominal Density | 72 kg/m³ (68–78 kg/m³) |
| Thermal Conductivity at 0 °C | ≤ 0.034 W/(m·K) |
| Thermal Conductivity at 20 °C | ≤ 0.036 W/(m·K) |
| Service Temperature | −50 °C to +110 °C |
| Fire Performance | B1 (GB 8624), Class 0 (BS 476 part 6 and 7) |
| Water Vapour Diffusion Resistance | ≥ 10,000, µ factor ≥ 7,000 |
| Water Absorption by Volume | ≤ 10 % |
| Oxygen Index | ≥ 32 % |
| Inner Diameter Range | 13–89 mm |
| Wall Thickness Range | 20–35 mm |
| Length per Piece | 2 m |
| Accessory | Contact adhesive and self-adhesive lap tape supplied |
| Application | Chilled water lines requiring anti-condensation performance |
| Packaging | Cartons / PE Bags |
| Minimum Order | 1 carton |
| Delivery Time | 15–20 days |
| Model | Inner Diameter (mm) | Wall Thickness (mm) | Length (m/piece) |
|---|---|---|---|
| FR-20X13 | 13 | 20 | 2 |
| FR-20X19 | 19 | 20 | 2 |
| FR-20X22 | 22 | 20 | 2 |
| FR-20X28 | 28 | 20 | 2 |
| FR-20X34 | 34 | 20 | 2 |
| FR-25X22 | 22 | 25 | 2 |
| FR-25X34 | 34 | 25 | 2 |
| FR-25X43 | 43 | 25 | 2 |
| FR-25X48 | 48 | 25 | 2 |
| FR-30X57 | 57 | 30 | 2 |
| FR-30X60 | 60 | 30 | 2 |
| FR-30X67 | 67 | 30 | 2 |
| FR-35X76 | 76 | 35 | 2 |
| FR-35X89 | 89 | 35 | 2 |
Model code format: FR-[wall thickness]X[inner diameter]. The 9 mm wall tube is supplied in 1.8 m pieces; all other walls in 2 m pieces. Special sizes and 40 mm wall tubes can be produced to order.
- Anti-condensation performance is delivered as a system: tube, adhesive and lap tape in the same closed cell material keep the vapour barrier continuous.
- High water vapour resistance above 10,000 stops the moisture take-up that destroys the performance of open cell insulation during plant shutdowns.
- Low thermal conductivity of 0.034 W/(m·K) reduces chilled water temperature rise, cutting pumping and chiller energy use.
- Walls up to 35 mm allow a dew point margin to be held in humid plant rooms and in unconditioned risers.
- Water absorption below 10 % by volume means the material survives washdown and accidental wetting without permanent loss of performance.
- B1 fire performance and Class 0 options meet the specification used on commercial risers and public buildings.
- Chilled water risers in humid climates
- Fan coil and air handling unit connections
- Primary chilled water mains in plant rooms
- Condensate and low temperature process lines
- Retrofit of sweating lines using slit tube and lap tape
In most cases the thickness is adequate but the vapour barrier is broken at joints, at hangers or at the ends near a valve. Re-seal every joint with contact adhesive, close the ends, and check that hangers do not pierce the tube. If the room humidity has changed, increase the thickness.
That condition needs a generous margin: 35 mm wall is typical for pipes up to 57 mm, and 25 mm may be enough for small diameters if air movement is low. Send us the design conditions and we will calculate the required thickness.
Contact adhesive on both faces gives the strongest vapour seal on butt joints. Self-adhesive lap tape is convenient for slit tube and for closing seams, and it should be applied over a clean, dry surface with a firm overlap.
Yes, cold water and chilled water behave the same way. Select the thickness against the pipe temperature and room condition, and seal all joints in the same way.