MYREAL Rubber Foam Pipe Insulation Hot Water and Cold Water Service Pipelines
Basic Properties
Trading Properties
| Product Name: | Dual Temperature Rubber Foam Pipe Insulation | Application: | Hot Water And Cold Water Pipelines |
|---|---|---|---|
| Inner Diameter: | 6-114 Mm | Wall Thickness: | 9-20 Mm |
| Nominal Density: | 70 Kg/m3 | Thermal Conductivity: | <=0.034 W/(m.K) At 0 C |
| Service Temperature: | -50 To +110 C | Ageing Performance: | K Value Change <5 % After 150 H |
| Colour Coding: | Red And Blue Options | Length Per Piece: | 2 M |
One insulation material for both hot water and cold water pipelines simplifies procurement, stock holding and site work. This rubber foam pipe insulation is rated for continuous service from -50 °C to +110 °C, so it covers domestic hot water, heating flow and return, and chilled or cold water services on the same project.
Stable thermal performance across that range is what makes the dual use practical. Thermal conductivity stays at or below 0.034 W/(m·K) at 0 °C and 0.036 W/(m·K) at 40 °C, and the change after accelerated ageing is under 5 %, so the design value does not have to be discounted for a hot line.
Excellent flexibility helps on refurbishment work, where pipe runs are interrupted by existing brackets, valves and cable trays. The tube can be compressed slightly to pass a tight gap and recovers its shape afterwards, keeping the closed cell wall and its vapour barrier intact.
Tubes are supplied from 6 mm to 114 mm inner diameter in 2 m pieces. For domestic water services, 9 mm to 13 mm wall is normally adequate, while heating mains and larger chilled lines use 15 mm to 20 mm. Wall thickness is selected per line, not per project, which keeps material cost aligned with the actual duty.
| Parameter | Specification |
|---|---|
| Product | MYREAL Rubber Foam Pipe Insulation Hot Water and Cold Water Service Pipelines |
| Model | FR-13X22 |
| Material | NBR/PVC elastomeric rubber foam, closed cell |
| Colour | Black, with red for hot and blue for cold identification |
| Nominal Density | 70 kg/m³ (65–75 kg/m³) |
| Thermal Conductivity at 0 °C | ≤0.034 W/(m·K) |
| Thermal Conductivity at 40 °C | ≤0.036 W/(m·K) |
| Service Temperature | -50 °C to +110 °C |
| Fire Performance | B1 (GB 8624) |
| Oxygen Index | ≥32 % |
| Water Vapour Diffusion Resistance | ≥10,000 |
| Ageing Performance | K value change <5 % after 150 h at 105 °C |
| Inner Diameter Range | 6–114 mm |
| Wall Thickness Range | 9–20 mm |
| Length per Piece | 2 m |
| Application | Hot water and cold water pipelines in building services |
| Colour Coding | Red and blue options for flow identification |
| Packaging | Cartons / PE Bags |
| Minimum Order | 1 carton |
| Delivery Time | 15–20 days |
| Model | Inner Diameter (mm) | Wall Thickness (mm) | Length (m/piece) |
|---|---|---|---|
| FR-09X06 | 6 | 9 | 1.8 |
| FR-09X10 | 10 | 9 | 1.8 |
| FR-09X13 | 13 | 9 | 1.8 |
| FR-09X16 | 16 | 9 | 1.8 |
| FR-09X19 | 19 | 9 | 1.8 |
| FR-09X22 | 22 | 9 | 1.8 |
| FR-13X16 | 16 | 13 | 2 |
| FR-13X22 | 22 | 13 | 2 |
| FR-13X28 | 28 | 13 | 2 |
| FR-13X34 | 34 | 13 | 2 |
| FR-15X19 | 19 | 15 | 2 |
| FR-15X22 | 22 | 15 | 2 |
| FR-20X43 | 43 | 20 | 2 |
| FR-20X48 | 48 | 20 | 2 |
| FR-20X60 | 60 | 20 | 2 |
| FR-20X76 | 76 | 20 | 2 |
| FR-20X89 | 89 | 20 | 2 |
| FR-20X108 | 108 | 20 | 2 |
| FR-20X114 | 114 | 20 | 2 |
Model code format: FR-[wall thickness]X[inner diameter]. The 9 mm wall tube is supplied in 1.8 m pieces; all other walls in 2 m pieces. Special sizes and 40 mm wall tubes can be produced to order.
- Stable thermal performance from -50 °C to +110 °C allows a single insulation type on heating, domestic hot water and cold water services.
- Excellent flexibility lets the tube pass brackets and existing services on refurbishment work and recover to a tight fit.
- A closed cell structure provides the vapour barrier on cold lines and prevents water take up on hot lines exposed to washdown.
- Ageing tests show a thermal conductivity change under 5 % after 150 hours at 105 °C, so the design thickness stays valid.
- Red and blue colour options identify flow and return lines without extra marking on site.
- Wall thicknesses from 9 mm to 20 mm match domestic services and larger heating mains from the same product family.
- Domestic hot water and cold water service pipes
- Heating flow and return pipework in residential and commercial buildings
- Heat pump and boiler connection pipework
- Rainwater and grey water lines needing condensation control
- Retrofit insulation of existing services in occupied buildings
Yes, provided the wall thickness is chosen for the duty. Cold lines need enough thickness to stay above dew point, hot lines need enough thickness to meet the heat loss target. The material itself is the same and the service range covers both.
Continuous service is rated to +110 °C, which covers stored hot water and secondary returns. For short term excursions above that, contact us before ordering so we can advise on a suitable product.
The material performs outdoors but should be protected from prolonged direct sunlight with a UV resistant tape or jacket. For exposed risers we recommend a foil faced finish to extend service life.
Friction holds the tube on most sizes. On vertical runs above 10 m, support the tube at intervals with a vapour sealed saddle or an adhesive collar so the weight is not carried by the joints.
Contact Person: Mrs. Betsy Ouyang
Tel: +86 177 4080 0950