MYREAL Closed Cell NBR Rubber Foam Pipe for Cold Storage Refrigeration Systems
Basic Properties
Trading Properties
| Product Name: | Closed Cell Moisture Resistant NBR Rubber Foam Pipe | Application: | Cold Storage Refrigeration Systems |
|---|---|---|---|
| Inner Diameter: | 13-89 Mm | Wall Thickness: | 20-40 Mm |
| Nominal Density: | 75 Kg/m3 | Thermal Conductivity: | <=0.034 W/(m.K) At 0 C |
| Service Temperature: | -50 To +105 C | Water Vapour Diffusion Resistance: | >=12,000 |
| Fire Rating: | B1 / Class 0 | Length Per Piece: | 2 M |
The MYREAL closed cell NBR rubber foam pipe is specified for cold storage, blast freezer and refrigeration plant where line temperatures sit between -45 °C and +5 °C and the vapour drive from warm ambient air into the insulation is severe. Under those conditions an open cell material fills with ice within one season; a closed cell tube does not.
The foam is an NBR/PVC compound with a nominal density of 75 kg/m³, which is higher than a general purpose tube because cold service demands more dimensional stability and a stronger vapour barrier. Thermal conductivity at 0 °C is 0.034 W/(m·K) or lower, so a 35 mm wall on a -40 °C suction line keeps the surface temperature above the dew point of the store room air.
Water vapour diffusion resistance above 12,000 is the number that matters on deep freeze duty. Every joint must be sealed with contact adhesive, and the tube ends at hangers and penetrations must be closed, because a cold line will pull moisture through any open seam.
Pieces are supplied in 2 m lengths from 12 mm to 114 mm inner diameter. For very large headers we can supply a wrapped board alternative, and our technical team will confirm the wall thickness against the operating temperature, ambient condition and pipe diameter before the order is confirmed.
| Parameter | Specification |
|---|---|
| Product | MYREAL Closed Cell NBR Rubber Foam Pipe for Cold Storage Refrigeration Systems |
| Model | FR-35X57 |
| Material | NBR/PVC elastomeric rubber foam, closed cell |
| Colour | Black |
| Nominal Density | 75 kg/m³ (70–80 kg/m³) |
| Thermal Conductivity at 0 °C | ≤0.034 W/(m·K) |
| Thermal Conductivity at -20 °C | ≤0.030 W/(m·K) |
| Service Temperature | -50 °C to +105 °C |
| Fire Performance | B1 (GB 8624), Class 0 (BS 476 part 6 and 7) |
| Oxygen Index | ≥32 % |
| Water Vapour Diffusion Resistance | ≥12,000, μ factor ≥8,000 |
| Water Absorption by Volume | ≤10 % |
| Inner Diameter Range | 13–89 mm |
| Wall Thickness Range | 20–40 mm |
| Length per Piece | 2 m |
| Application | Cold storage, blast freezer and refrigeration suction lines |
| Low Temperature Flexibility | No cracking at -50 °C |
| Packaging | Cartons / PE Bags |
| Minimum Order | 1 carton |
| Delivery Time | 15–20 days |
| Model | Inner Diameter (mm) | Wall Thickness (mm) | Length (m/piece) |
|---|---|---|---|
| FR-20X13 | 13 | 20 | 2 |
| FR-20X16 | 16 | 20 | 2 |
| FR-20X19 | 19 | 20 | 2 |
| FR-20X22 | 22 | 20 | 2 |
| FR-20X28 | 28 | 20 | 2 |
| FR-25X22 | 22 | 25 | 2 |
| FR-25X28 | 28 | 25 | 2 |
| FR-25X34 | 34 | 25 | 2 |
| FR-30X43 | 43 | 30 | 2 |
| FR-30X48 | 48 | 30 | 2 |
| FR-35X57 | 57 | 35 | 2 |
| FR-35X60 | 60 | 35 | 2 |
| FR-35X67 | 67 | 35 | 2 |
| FR-40X76 | 76 | 40 | 2 |
| FR-40X89 | 89 | 40 | 2 |
Model code format: FR-[wall thickness]X[inner diameter]. The 9 mm wall tube is supplied in 1.8 m pieces; all other walls in 2 m pieces. Special sizes and 40 mm wall tubes can be produced to order.
- Closed cell moisture resistance keeps the insulation dry in cold rooms, where open cell materials saturate and lose insulation value within weeks.
- Low thermal conductivity of 0.034 W/(m·K) at 0 °C and 0.030 W/(m·K) at -20 °C limits compressor run time on freezer lines.
- Effective condensation control comes from a vapour resistance above 12,000 combined with closed cell geometry, so no separate vapour barrier jacket is required.
- A density of 75 kg/m³ holds the tube shape on vertical drops and around hangers in a cold store, where softer foam would compress and thin out.
- Low temperature flexibility down to -50 °C means the tube can still be fitted inside a freezer room without cracking.
- Available up to 114 mm inner diameter and 40 mm wall for large suction headers and pump lines.
- Cold storage and freezer room suction and liquid lines
- Blast freezer and spiral freezer pipework
- Refrigeration racks, condensers and pump lines
- Dairy, meat and seafood processing plant piping
- Ice rink and process cooling distribution lines
At -40 °C the insulation sees a large temperature difference and a strong vapour drive from the store room air. The 75 kg/m³ grade has a tighter cell structure and better dimensional stability, so it resists compression at hangers and keeps the vapour barrier continuous for the life of the plant.
For a -40 °C line in a store room at -18 °C with 80 % relative humidity, 35 mm wall is the usual selection for pipe sizes up to 57 mm, and we confirm it with a condensation and heat gain calculation. Where the line passes into a warmer area, add a vapour sealed transition and increase the thickness.
Yes. Every butt joint and every termination should be closed with contact adhesive applied to both faces, and hangers should carry a load bearing insert or a vapour sealed saddle. A continuous vapour barrier is the single most important installation detail on cold service.
Standard supply is 2 m straight pieces, which suit most plant rooms. For long continuous runs we can discuss coil supply or factory fitted self-adhesive lap so fewer field joints are needed.
Contact Person: Mrs. Betsy Ouyang
Tel: +86 177 4080 0950