Fire Classification in Facade Tenders: Reading EN 13501-1 Correctly
Short answer: A2-s1,d0 reports how a product behaved in a set of small-scale fire tests. It is not an approval of the facade. On a tall building the insulation inside the same wall is often required to reach A2-s3,d2 while the outer surface must reach A2-s1,d0, so one wall carries two different strings. Read class, component and building height as three separate requirements, then decide whether the tender asked for a product classification or a system test.
A2-s1,d0 combines a main class with smoke (s) and flaming droplet (d) additions. Dropping either suffix makes the requirement unverifiable: B-s1,d0 and B-s3,d2 describe materially different behaviour.
The criteria sit in Commission Delegated Regulation (EU) 2016/364, reproducing the EN 13501-1 tables. A1 requires EN ISO 1182 to show a rise of 30 °C or less, mass loss of 50% or less and no sustained flaming, with calorific potential to EN ISO 1716 of 2.0 MJ/kg or less. A2 allows a 50 °C rise, flaming up to 20 s and a calorific potential of 3.0 MJ/kg, or a fire growth rate index (FIGRA) of 120 W/s or less in EN 13823, lateral spread below the specimen edge and total heat release of 7.5 MJ over 600 s.
B adds EN ISO 11925-2 at 30 s to those thresholds; D relaxes FIGRA to 750 W/s.
The smoke suffix is quantitative: s1 requires a smoke growth rate of 30 m²/s² or less and total smoke production of 50 m² or less; s2 allows 180 and 200; s3 is below both. d0 requires no flaming droplets.
UK guidance separates components explicitly. In Approved Document B, volume 2, regulation 7(2) requires materials forming an external wall, or a specified attachment, of a "relevant building" to be A2-s1,d0 or A1. A relevant building has a storey at least 18 m above ground level and contains dwellings, an institution or a room for residential purposes.
Paragraph 12.6 addresses insulation separately: in a building with a storey 18 m or more, any insulation product or filler in an external wall should be class A2-s3,d2 or better. Paragraph 12.7 sets A2-s1,d0 for insulation in residential buildings from 11 m. Table 12.1 adds a third layer for the outermost surface, varying by building type, height and distance to the boundary.
Two consequences follow. A tender that writes "A2-s1,d0 throughout" over-specifies the insulation and, more often, copies the surface requirement onto a component nobody checked. The s1 and s3 difference is smoke, not fire growth: the guidance permits more smoke from insulation than from the visible surface.
EN 13823 places a corner specimen in a laboratory hood and measures heat release, lateral spread, smoke and droplets on that specimen. It does not reproduce a multi-storey wall with a ventilated cavity, window openings, continuous vertical channels or a rainscreen acting as a chimney.
That gap is why facade rules use a second route. Approved Document B allows external walls to comply either with its component provisions or by meeting the performance criteria of BRE report BR 135 using full-scale data from BS 8414-1 or BS 8414-2. In the United States, NFPA 285 evaluates fire propagation characteristics of exterior wall assemblies containing combustible components — an assembly, not a product.
For tender review the implication is direct. A product report proves what a board or a foam does in a bench test; it cannot be extrapolated to a different cavity depth, fixing pattern or membrane. When a submission offers a product certificate as evidence for a facade, the missing document is the system test report with the tested build-up.
- "Class A" with no standard named. In China that means GB 8624; in the United States it often means an ASTM E84 flame spread band; in Europe it is not a class at all.
- A main class without suffixes. "Class B" does not say whether smoke is s1, s2 or s3, or whether the product drips.
- A surface class applied to insulation. The clause must name the component that receives the class.
- A product certificate offered as system approval. Ask for the build-up, the test standard and the report number.
- No height or use trigger. The same material can be acceptable at 10 m and unacceptable at 30 m.
Adding a report reference and revision date to each line closes most gaps before submission, and lets a reviewer trace the class string to a standard, a report and the drawing detail it was tested against.
Values come from current MYREAL literature and describe the named product, not an assembled wall.
| Product | Declared fire performance | Basis stated in the datasheet |
|---|---|---|
| Foam glass | Non-combustible, Class A1 | EN 13501-1:2007 |
| Rock wool | Class A | GB 8624 |
| Glass wool | Class A | GB 8624 |
| Calcium silicate | Class A1 | GB/T 8624 |
| Ceramic foam board | A1-grade non-combustibility; heat of combustion ≤2.0 MJ/kg | GB/T 14402 |
| XPS | Class B2 to B1 | GB 8624 |
| PIR | Flame spread below 25; oxygen index ≥30 | ASTM E84; GB/T 2406.2 |
| Foam rubber | Fire retardant B1; oxygen index ≥32% | Manufacturer declaration |
GB 8624 and EN 13501-1 are separate systems with separate test programmes, so a GB 8624 report is not a declaration of performance to EN 13501-1, even where the letters look familiar. ASTM E84 reports a comparative flame spread index and states in its own scope that it does not classify a material as non-combustible.
A workable clause names four things per component: the class including both suffixes, the test standard behind it, the evidence document, and the height or use condition that triggers the requirement. One sentence is enough: "External wall insulation in buildings with a storey 18 m or more above ground level shall achieve class A2-s3,d2 or better to EN 13501-1, evidenced by a classification report and a declaration of performance for the product supplied."
Two further conditions prevent most disputes. Any change to the build-up — cavity depth, membrane, fixing, substrate — should require re-submission, because a system result belongs to the assembly that was tested. And the tender should state whether a BS 8414 or NFPA 285 route is acceptable, so a compliant system is not rejected for lacking a component class it never needed. The clause plus a marked-up build-up drawing removes the two arguments that consume most technical reviews: which component the class belongs to, and which document proves it.
No. GB 8624 Class A, a US Class A flame spread rating based on ASTM E84 and EN 13501-1 A1 are three labels from three systems. Only the last is an EN 13501-1 class, and even then A1 and A2 are distinct levels.
They are different components with different exposure. The visible surface is ignited first and produces the visible smoke, so its smoke class is tighter. Insulation sits behind a surface and a cavity, where more smoke is accepted in exchange for limiting fire growth.
Class is only one condition. Rock wool and glass wool are routinely declared Class A to GB 8624, and non-combustible products can meet A1 or A2, but the project still needs the declared EN class, the correct component requirement and, where the alternative route is used, a system test for the actual build-up.