MYREAL Closed Cell Rubber Foam Pipe Thermal Insulation Tube for HVAC Systems
Basic Properties
Trading Properties
| Product Name: | Closed Cell Stable Rubber Foam Pipe | Application: | HVAC Systems |
|---|---|---|---|
| Inner Diameter: | 6-114 Mm | Wall Thickness: | 13-30 Mm |
| Nominal Density: | 70 Kg/m3 | Thermal Conductivity: | <=0.034 W/(m.K) At 0 C |
| Service Temperature: | -50 To +110 C | Fire Rating: | B1 / Class 0 |
| Vapour Diffusion Resistance: | >=10,000 | Length Per Piece: | 2 M |
The MYREAL closed cell rubber foam pipe insulates chilled water, hot water and refrigerant lines in HVAC plant rooms, risers and equipment connections. Tubes are supplied in nominal inner diameters from 6 mm to 114 mm with wall thickness from 13 mm to 30 mm, and each piece is 2 m long, so a riser run can be completed with a small number of joints and very little offcut waste.
Thermal conductivity of the foam is 0.034 W/(m.K) or lower at 0 °C. On a 7 °C chilled water line inside a conditioned plant room, a 20 mm wall keeps the outer surface above dew point, which is the thickness most HVAC consultants specify for indoor pipework. Because every cell in the wall is closed, that value does not drift upward as the pipework ages and as moisture cycles through the building.
The tube is flexible enough to be pushed over elbows, valve bodies and pump flanges and can be trimmed with a sharp knife on site, so installation does not depend on prefabricated sections. Slit and self-seal versions are available for lines that are already in service, where the pipe cannot be disconnected.
MYREAL Energy Saving (Shanghai) Co., Ltd has produced elastomeric pipe insulation since 2009 for HVAC contractors in Europe, the Middle East and Southeast Asia. Density, thermal conductivity and fire performance are tested on every batch, and the batch test report travels with the shipping documents so a project engineer can verify the delivered material against the specification.
| Product | MYREAL Closed Cell Rubber Foam Pipe Thermal Insulation Tube for HVAC Systems |
|---|---|
| Model | FR-20X22 |
| Material | NBR/PVC elastomeric rubber foam |
| Colour | Black (grey, red and blue on request) |
| Nominal Density | 70 kg/m³ (65–75 kg/m³) |
| Thermal Conductivity at 0 °C | ≤0.034 W/(m.K) |
| Thermal Conductivity at 40 °C | ≤0.036 W/(m.K) |
| Service Temperature | −50 °C to +110 °C |
| Fire Performance | B1 (GB 8624), Class 0 (BS 476 part 6 and 7) |
| Oxygen Index | ≥32 % |
| Water Vapour Diffusion Resistance | ≥10,000, μ factor ≥7,000 |
| Water Absorption by Volume | ≤10 % |
| Inner Diameter Range | 6–114 mm |
| Wall Thickness Range | 13–30 mm |
| Length per Piece | 2 m (1.8 m and 2.2 m on request) |
| Application | HVAC systems: chilled water, hot water and refrigerant pipework |
| Compression Recovery at 50 %, 72 h | ≥70 % |
| Dimensional Stability at 105 °C, 7 days | ≤10 % |
| Packaging | Cartons / PE Bags |
| Minimum Order | 1 carton |
| Delivery Time | 15–20 days |
| Model | Inner Diameter (mm) | Wall Thickness (mm) | Length (m/piece) |
|---|---|---|---|
| FR-13X06 | 6 | 13 | 2 |
| FR-13X10 | 10 | 13 | 2 |
| FR-13X13 | 13 | 13 | 2 |
| FR-13X16 | 16 | 13 | 2 |
| FR-13X19 | 19 | 13 | 2 |
| FR-13X22 | 22 | 13 | 2 |
| FR-13X28 | 28 | 13 | 2 |
| FR-15X13 | 13 | 15 | 2 |
| FR-15X19 | 19 | 15 | 2 |
| FR-20X22 | 22 | 20 | 2 |
| FR-20X34 | 34 | 20 | 2 |
| FR-20X43 | 43 | 20 | 2 |
| FR-25X60 | 60 | 25 | 2 |
| FR-25X76 | 76 | 25 | 2 |
| FR-30X89 | 89 | 30 | 2 |
| FR-30X108 | 108 | 30 | 2 |
| FR-30X114 | 114 | 30 | 2 |
Model code format: FR-[wall thickness]X[inner diameter]. The 9 mm wall tube is supplied in 1.8 m pieces, all other walls in 2 m pieces. Special sizes and 40 mm wall tubes can be produced to order.
- A closed cell structure means each bubble in the wall is sealed, so the tube holds its low thermal conductivity of 0.034 W/(m.K) instead of absorbing plant room moisture.
- Stable thermal performance across the whole service range of −50 °C to +110 °C allows one insulation type on chilled water, condenser water and low pressure hot water lines.
- Water vapour diffusion resistance above 10,000 blocks the vapour drive that causes dripping pipes and corrosion under insulation on cold lines.
- B1 fire performance and an oxygen index of at least 32 % suit plant rooms, risers and occupied buildings where a fire rated pipe insulation is mandatory.
- Flexible wall thicknesses from 13 mm to 30 mm let the designer match insulation to pipe diameter and dew point margin without switching product families.
- Tubes are cut to 2 m and packed in cartons or PE bags by size, and each package is marked with the inner diameter and wall thickness for fast checking on site.
- Chilled water supply and return pipework in plant rooms and risers
- Low pressure hot water heating lines and fan coil connections
- Condenser water and heat pump pipework
- Refrigerant suction and liquid lines in split and packaged units
- Valve, strainer and pump body insulation in mechanical rooms
For an indoor line at 7 °C with 25 to 28 °C room air and 60 % relative humidity, 20 mm wall is normally enough to keep the surface above dew point. For high humidity plant rooms or outdoor runs we recommend 25 mm or 30 mm, and we can run the condensation calculation for the actual design conditions on request.
Yes. The service range of −50 °C to +110 °C covers both duties, and the closed cell structure performs the same way on hot service. For lines above 90 °C we recommend checking support spacing and using a self-adhesive lap seal at the joints.
Butt fit the tube ends, seal the seam with contact adhesive or the self-adhesive lap, and close the ends at flanges with the same adhesive. This keeps a continuous vapour barrier on chilled lines, which is what protects the thermal performance long term.
Every batch carries a test report for density, thermal conductivity, fire performance and dimensional stability. The report number is printed on the carton label, so any question on delivered material can be traced back to the production record.