Heavy Duty Calcium Silicate Equipment Board For High Temperature Plant Insulation
Basic Properties
Trading Properties
| Product Type: | Rigid Board | Material: | Hydrous Calcium Silicate From Inorganic Siliceous And Calcareous Materials |
|---|---|---|---|
| Density Grade: | 240 Kg/m3 (MY240) | Dimension: | 1000 X 500 Mm, THK 25-100 Mm |
| Maximum Service Temperature: | 650 C | Thermal Conductivity: | 0.087 W/(m.K) At 300 C |
| Compressive Strength: | >= 0.40 MPa (MY150/170) / >= 0.65 MPa (MY220/240/270) | Flexural Strength: | >= 0.20 MPa (MY150/170) / >= 0.33 MPa (MY220/240/270) |
| Dimensional Stability: | <= 1% | Linear Shrinkage: | <= 2% |
| Moisture Content: | <= 7.5% | Fire Performance: | GB/T 8624 Class A1 Non-combustible |
| Chloride Ion: | Super Low, Suitable For Stainless Steel Pipework | Application: | Heat Exchanger Shell And Channel Insulation |
| Moistureresistance: | Good | Applications: | Construction, Insulation Boards, Refractory Materials |
| Appearance: | White Powder Or Granular | Density: | 2.2 - 2.6 G/cm³ |
| Fireresistance: | Excellent | Phvalue: | Alkaline (around 11-12) |
| Waterabsorption: | Low | Chemicalformula: | Ca2SiO4 |
| Compressivestrength: | High | Insulationproperty: | Good Thermal Insulation |
| Meltingpoint: | 1540 °C | Stability: | Chemically Stable Under Normal Conditions |
| Thermalconductivity: | 0.06 - 0.10 W/m·K | Productname: | Calcium Silicate |
| Toxicity: | Non-toxic |
MYREAL industrial equipment calcium silicate board is the MY240 general purpose grade for vessels, heat exchangers, tanks and process equipment. It provides a rigid, cut-to-shape insulation layer that keeps a constant thickness over nozzles, manways and irregular geometry, and its low water absorption keeps performance stable in humid plant conditions.
Technical Data
Application
Applied to high temperature vessels, exchangers, tanks and process equipment in petroleum refining, chemical and city heat supply facilities.
- Heat exchanger shell and channel insulation
- Process vessel and reactor insulation
- Storage tank and hot water tank insulation
- Valve, flange and nozzle box insulation
- Industrial dryer and calender insulation
Key Advantages
- MY240 grade with 0.65 MPa compressive strength for plant equipment duty.
- Cuts cleanly to nozzles, manways and irregular profiles.
- Constant thickness over the equipment surface, no compression points.
- Low water absorption, performance is not affected by humidity.
- Class A1 non-combustible for plant fire safety requirements.
Standards and Compliance
- Manufactured to GB/T 5486 calcium silicate products standard under an ISO 9001 certified quality system
- GB/T 8624 Class A1 non-combustible, no flame spread and no dense smoke
- Super low chloride ion content protects stainless steel and alloy pipework from chloride stress corrosion
- Low water absorption, performance is not affected by humidity
- Free of formaldehyde, benzene and other harmful substances
- Special shaped parts can be customized to your drawing
Installation Notes
- Cut panels to the equipment profile and dry fit before fixing.
- Fix with studs, bands or high temperature adhesive.
- Fill small gaps with high temperature sealant or ceramic fiber.
- Clad with sheet metal for mechanical and weather protection.
FAQ
Contact Person: Mrs. Betsy Ouyang
Tel: +86 17740800950